How do I select a circuit breaker for PAT-T series?
Let’s take 8 kW type as an example. Its input current is 32 A (MAX) so that take the breaker capacity margin by 20 % to allow for safe operation. Therefore, select a 40-A or 50-A three-phase breaker.