KHA1000_Specifications

KHA3000KHA1000
Common input specificationsMaximum input voltage600 Vrms / 900 Vpeak (CAT I), 400 Vrms (CAT II)300 Vrms / 560 Vpeak (CAT I), 250 Vrms (CAT II)
Maximum input current40 Arms / 100 Apeak, whichever is smaller 160 Apeak (within 20 ms)24 Arms / 50 Apeak, 80 Apeak (within 20 ms)
Number of input channels3 channels for both voltage input and current input (L1, L2 and L3)1 channels for both voltage input and current input
Voltage measurement input switchingSingle-phase 2-wire, single-phase 3-wire, three-phase 3-wire and three-phase 4-wireSingle-phase 2-wire
Voltage measurement functionRated voltage for the range150 V/300 V/600 V150 V/300 V
Allowable crest factor2
Display itemTrueRMS and ±peak
Accuracy± (0.4 % of rdng +0.04 % of range)
Current measurement functionRated current for the range0.5 A/1 A/2 A/5 A/10 A/20 A/ 40 A0.5 A/1 A/2 A/5 A/10 A/20 A
Allowable crest factor0.5 A to 20 A range: 4, 40 A range: 2.5 and 4 (up to 20 ms)0.5A to 10 A range: 4, 20 A range:2.5
Accuracy *145 Hz to 65 Hz0.5 A range: ± (0.5 % of reading +0.2 % of range) 1 A to 40 A range: ± (0.5 % of reading +0.1 % of range)0.5 A range: ± (0.5 % of reading +0.2 % of range) 1 A to 20 A range: ± (0.5 % of reading +0.1 % of range)
66 Hz to 2.4 kHz0.5 A range: ± ((0.5 +0.417 ×n kHz) % of reading +0.2 % of range) 1 A to 40 A range: ± ((0.5 +0.417 ×n kHz) % of reading +0.1 % of range)0.5 A range: ± ((0.5 +0.417 ×n kHz) % of reading +0.2 % of range) 1 A to 20 A range: ± ((0.5 +0.417 ×n kHz) % of reading +0.1 % of range)
Power measurement functionDisplay itemEffective power, apparent power, reactive power and power factor
Effective power accuracyP ≥ 150 W (±1 % of range) , P < 150 W (±1.5 W)
Frequency measurement functionMeasurement inputIndependent measurement of frequencies for voltages of L1, L2 and L3Measurement of frequency for voltage
Measurement frequency range / accuracy / resolution45Hz〜65Hz/±(0.15% of reading+2digits)/0.001Hz
Phase measurement functionMeasurement itemsVoltage/current phases, line voltage phase *2 and harmonic phase
Measuring range/resolution0.00° to 359.99° / 0.01°
Harmonic current measurement functionCompliant standardsIEC 61000-3-2 Ed5.0, IEC 61000-3-2 Ed3.0, IEC 61000-3-2Ed2.2, JIS C61000-3-2(2019), JIS C61000-3-2(2005), IEC 61000-3-12 Ed2.0, IEC 61000-3-12 Ed1.0IEC 61000-3-2 Ed5.0(2018), IEC 61000-3-2 Ed2.2(2004), IEC 61000-3-2 Ed3.0(2005), JIS C61000-3-2(2003), JIS C61000-3-2(2005), JIS C61000-3-2(2019)
Requirements for measuring instrument standardIEC 61000-4-7 Ed2.1(2009), IEC 61000-4-7 Ed2.0(2002), IEC 61000-4-7 Ed1.0(1991)
Harmonic analysis order40 th (HA mode), 180 th (OTHER mode)
Interharmonics processingProcessing ON (2nd order and more): IEC 61000-4-7 Ed2.1(2009), Processing ON: IEC 61000-4-7 Ed2.0(2002)
Processing OFF: IEC 61000-4-7 Ed1.0(1991)
Window functionRectangular
Window width10 cycles(50 Hz) 12 cycles(60 Hz), 16 cycles(50 Hz/60 Hz)
Anti-aliasing filterCutoff frequency: 6 kHz, 4 th Butterworth type (HA mode), 15 kHz 4 th Butterworth type (Other mode)
Class D judgment functionCurrent waveform inclusion rate of 95 % or more
(equivalent to JIS C61000-3-2:2003 Class D) *3
Harmonic voltage measurement functionMeasurement itemsVoltage, frequency and voltage harmonic inclusion rate
Voltage harmonic analysis order40 th
Flicker/voltage fluctuation analysis functionCompliant standardsIEC 61000-3-3 Ed3.1(2017), IEC 61000-3-3 Ed2.0(2008) *2, IEC 61000-3-11 Ed2.0(2007) *2
Requirements for measuring instrument standardIEC 61000-4-15 Ed2.0(2010), IEC 61000-4-15 Ed1.1(2003)
FlickerPst accuracy1 ± 5 %
Pst measurement time30 to 900 seconds
Voltage fluctuationMeasurement methodSelectable between simultaneous measurement with Pst and independent measurement
dmax measurement of manual switching equipment 3 to 24 times (Measuring time for each time: 30 to 180 seconds)
General measurement functionCurrent/voltage waveform monitor, FFT analyzer and In-rush current measurement
Communication interfaceGPIB, RS232C, and USB interfaces are equipped as standard.
Removal data storageSupported mediaCompact Flash memory card (CF card) *4, maximum capacity: 512 MB, USB Memory*2, maximum capacity: 16 GB
External equipment control functionPCR-LE control (RS232C)Voltage, frequency, range, ON phase, OUTPUT ON and OFF
Power supplyNominal voltage range100 V to 240 V AC 50 Hz to 60 Hz
Environmental conditionsOperating temperature and humidity ranges0 °C to +40 °C (+32 °F to +104 °F), 20 %rh to 80 %rh (no condensation)
Withstanding voltage1500 VAC, 1 minute (AC input ↔ chassis),
3550 VAC, 1 minute (measuring terminal ↔ chassis)
1500 VAC, 1 minute
Dimensions Unit: mm (inches)430(16.93)(455(17.91))W × 177(6.97)(195(7.68))H × 270(10.63)(330(12.99))D mm(inch)
WeightApprox. 10 kg (22.05 lb)Approx. 8 kg
SafetyConforming to the following standard requirements: IEC 61010-1:2001 (Class I, Pollution degree 2)
Electromagnetic compatibilityIEC61326-1 A3:2003
AccessoriesPower cord, voltage sensing terminal plug and short-circuit wire kit (with a dedicated screwdriver), spare fuse and operation manual

*1: n = indicates frequency. *2: Only Model KHA3000. *3: Users are requested to prepare the CF card. Note that the maximum supported capacity of a CF card is 512 MB.