Item/Model | PBZ20-60 SR | PBZ20-80 SR | PBZ20-100 SR | PBZ40-30 SR | PBZ40-40 SR | PBZ40-50 SR | |
---|---|---|---|---|---|---|---|
Input rating | Nominal input voltage | 200 Vac to 240 Vac, single phase | |||||
Voltage range | 180 Vac to 250 Vac | ||||||
Frequency range | 47 Hz to 63 Hz | ||||||
Current | 15 Aac or less | 20 Aac or less | 25 Aac or less | 15 Aac or less | 20 Aac or less | 25 Aac or less | |
Inrush current | 120 Apeak or less | 160 Apeak or less | 200 Apeak or less | 120 Apeak or less | 160 Apeak or less | 200 Apeak or less | |
Power | 2700 VA or less | 3600 VA or less | 4500 VA or less | 2700 VA or less | 3600 VA or less | 4500 VA or less | |
Power factor | 0.95 TYP (when the input voltage is 200 V) | ||||||
Output rating | Power | 1200 W | 1600 W | 2000 W | 1200 W | 1600 W | 2000 W |
Voltage | ±20 V | ±40 V | |||||
Current | ±60 A | ±80 A | ±100 A | ±30 A | ±40 A | ±50 A | |
Output terminal | Output terminal | Rear panel output terminals | |||||
Isolation voltage | 500 Vdc Only the output’s COM terminal can be grounded. |
Item/Model | PBZ60-20.1 SR | PBZ60-26.8 SR | PBZ60-33.5 SR | PBZ80-15 SR | PBZ80-20 SR | PBZ80-25 SR | |
---|---|---|---|---|---|---|---|
Input rating | Nominal input voltage | 200 Vac to 240 Vac, single phase | |||||
Voltage range | 180 Vac to 250 Vac | ||||||
Frequency range | 47 Hz to 63 Hz | ||||||
Current | 15 Aac or less | 20 Aac or less | 25 Aac or less | 15 Aac or less | 20 Aac or less | 25 Aac or less | |
Inrush current | 120 Apeak or less | 160 Apeak or less | 200 Apeak or less | 120 Apeak or less | 160 Apeak or less | 200 Apeak or less | |
Power | 2700 VA or less | 3600 VA or less | 4500 VA or less | 2700 VA or less | 3600 VA or less | 4500 VA or less | |
Power factor | 0.95 TYP (when the input voltage is 200 V) | ||||||
Output rating | Power | 1206 W | 1608 W | 2010 W | 1200 W | 1600 W | 2000 W |
Voltage | ±60 V | ±80 V | |||||
Current | ±20.1 A | ±26.8 A | ±33.5 A | ±15 A | ±20 A | ±25 A | |
Output terminal | Output terminal | Rear panel output terminals | |||||
Isolation voltage | 500 Vdc Only the output’s COM terminal can be grounded. |